The current rating, or ampacity, of a cable is the steady current it can carry without its conductor exceeding a maximum temperature. For cross-linked polyethylene (XLPE) insulation that limit is 90 °C in continuous service, which is why XLPE cables carry more current than PVC cables of the same size. In June 2017 the original page on this address was a quick reference to manufacturers’ rating tables for large single-core and multicore XLPE cables, gathered for a motor control centre upgrade. This version explains what lies behind such tables and how to apply them correctly.
Why temperature sets the rating
Every ampere through a conductor of AC resistance R produces I²R watts of heat per metre. That heat must flow out through the insulation, any bedding, sheath and armour, and then into the surrounding air or soil. Each layer has a thermal resistance. At steady state, the temperature rise of the conductor above ambient is proportional to the heat generated, so:
I ∝ √(Δθ / (R × T_total))
where Δθ is the permitted rise from ambient to the conductor limit and T_total is the total thermal resistance to the surroundings. Anything that raises ambient temperature or thermal resistance, or that adds heat from neighbouring cables, reduces the current the cable can carry.
The key temperature limits for common insulation types are:
| Insulation |
Max. continuous conductor temperature |
Max. short-circuit temperature (≤ 5 s) |
| PVC (general purpose) |
70 °C |
160 °C (up to 300 mm²) |
| XLPE / EPR (thermosetting) |
90 °C |
250 °C |
What determines the ampacity
1. Installation method. IEC 60364-5-52 (and BS 7671 Appendix 4, which follows the same structure) tabulates ratings by reference method: enclosed in conduit in an insulated wall, clipped direct, on perforated tray, in free air, in ducts or direct in the ground. The same cable may have ratings that differ by tens of per cent between methods because heat escapes more easily in free air than in an insulated wall.
2. Ambient air temperature. IEC tables assume 30 °C air for cables in air. In a hot plant room or roof space the correction factor is below 1.
3. Ground temperature, depth and soil thermal resistivity. For buried cables the IEC reference conditions are 20 °C ground temperature and a soil thermal resistivity of 2.5 K·m/W, with separate correction tables for each. Dry sandy soil can have higher resistivity than the reference; moist clay lower. Backfill quality matters as much as the cable size.
4. Grouping. Cables installed together heat each other. Group factors depend on the number of circuits and whether they are bunched, spaced, or arranged on trays or ladders.
5. Number of loaded conductors and harmonics. Ratings are given for two or three loaded conductors. In four-core cables feeding non-linear loads, triplen harmonic currents add in the neutral, which then carries current and generates heat; BS 7671 Appendix 4 gives a method for this.
6. Construction. Single-core cables in trefoil touching run hotter than when spaced, but spacing raises inductance and sheath currents. Single-core AC cables use non-magnetic (aluminium wire) armour to avoid eddy-current heating in the armour; multicore cables can use steel wire armour because the phase currents’ magnetic fields largely cancel.
Correction factors are derived from the same physics
The ambient-temperature factors in IEC 60364-5-52 closely follow:
Ca = √((θmax − θa) / (θmax − θref))
For XLPE in air (θmax = 90 °C, θref = 30 °C):
| Ambient |
Calculated Ca |
PVC equivalent (θmax = 70 °C) |
| 35 °C |
0.96 |
0.94 |
| 40 °C |
0.91 |
0.87 |
| 45 °C |
0.87 |
0.79 |
| 50 °C |
0.82 |
0.71 |
For buried XLPE (θref = 20 °C), the same expression gives about 0.96 at 25 °C ground temperature and 0.93 at 30 °C. These calculated values are a guide to understanding; always use the factors in the edition of the standard you are designing to. The higher operating temperature of XLPE makes it noticeably less sensitive to hot ambients than PVC, which is significant in tropical plant rooms.
Worked derating example (illustrative)
A 110 kW pump motor at 415 V, power factor 0.87 and efficiency 0.95 is to be fed from a motor control centre in a plant room where the design ambient is 40 °C. The cable shares a bunched route with one other circuit (two circuits in total).
Step 1: design current.
Ib = P / (√3 × V × PF × η) = 110,000 / (√3 × 415 × 0.87 × 0.95) ≈ 185 A
Step 2: protective device. Choose In ≥ Ib, say a 200 A device.
Step 3: rating factors.
Ca (40 °C, XLPE) = 0.91
Cg (two circuits bunched) = 0.80 (typical tabulated value; confirm for the arrangement used)
Step 4: required tabulated rating.
It ≥ In / (Ca × Cg) = 200 / (0.91 × 0.80) ≈ 275 A
Select the smallest cable whose tabulated rating, for the correct reference method and number of loaded conductors, is at least 275 A. If, for illustration, a candidate cable had a tabulated rating of 300 A:
Iz = It × Ca × Cg = 300 × 0.91 × 0.80 ≈ 218 A ≥ In = 200 A ✓
The rule to satisfy is Ib ≤ In ≤ Iz, with the device’s operating characteristics also checked against overload criteria of the standard in use.
Step 5: other checks. Current rating is only one constraint. Also check:
- Voltage drop at full load and, for direct-on-line motors, at starting current.
- Short-circuit withstand using the adiabatic equation
S ≥ √(I²t) / k. For copper XLPE (90 °C to 250 °C), k = 143. A fault of 20 kA cleared in 0.2 s needs S ≥ 20,000 × √0.2 / 143 ≈ 63 mm².
- Earth fault loop impedance, so the protective device disconnects in the required time.
When tables are not enough: IEC 60287
The tables in IEC 60364-5-52 cover common low-voltage installations. For medium- and high-voltage cables, unusual installations (deep burial, long ducts, cable tunnels, crossings with other heat sources) or high-value circuits, ratings are calculated with IEC 60287. For a buried AC cable its steady-state equation is:
I = √{ [Δθ − Wd(0.5·T1 + n(T2 + T3 + T4))] / [R·T1 + n·R(1 + λ1)·T2 + n·R(1 + λ1 + λ2)(T3 + T4)] }
where R is the AC resistance at operating temperature, Wd the dielectric loss, T1 to T4 the thermal resistances of insulation, bedding, outer covering and surroundings, n the number of conductors, and λ1, λ2 the sheath and armour loss factors. Manufacturers’ published ratings are normally derived this way for stated conditions, which is why those conditions must match the actual installation.
Variable frequency drives and cable heating
The original note was written during a change from resistance starters to variable frequency drives. Drives change the cable duty: the motor cable carries a switched waveform with high-frequency components, and the supply cable carries harmonic currents. Drive manufacturers generally specify symmetrical, screened motor cables and maximum lengths, and harmonic currents in the supply side may justify extra derating or filtering. Harmonics also interact with power factor correction capacitors, discussed in calculating power factor from meter readings. For surge exposure of long cable runs, see the explainer on lightning and surge protection.
What has changed since
BS 7671 has been revised since 2017, with the 18th Edition (BS 7671:2018) and subsequent amendments; Appendix 4 retains the same rating-factor method. The physics and the design sequence above are unchanged. Cable-sizing software now routinely implements the IEC tables and IEC 60287 calculations, but its output is only as good as the installation conditions entered, so ambient temperature, grouping and soil assumptions should still be checked against the site.